1️⃣ Circuit Breaker (MCB)
- Recommended Model: C16A, 3-pole miniature circuit breaker
 - Type: Curve C (suitable for motor starting current surges)
 - Function: Provides short-circuit and overload protection; acts as the main power cut-off
 
2️⃣ Thermal Overload Relay
- Current Setting: 5A
(Rated current of the motor is around 4.2–4.5A, so setting slightly above is ideal) - Installation: Connected below the contactor or within the motor control circuit
 - Function: Protects the motor from damage due to prolonged overload
 
3️⃣ Starting Method
- Type: Direct On Line (DOL) starting
 - Usage: Suitable for small motors like 2.2kW; no need for soft starter or star-delta starting
 
4️⃣ Cable Selection
| Circuit | Recommended Cable Size | Notes | 
|---|---|---|
| Main Power | 3 × 2.5mm² copper wire | For 3-phase wires (L1/L2/L3) | 
| Grounding Wire | 1 × 1.5mm² yellow-green copper wire | For protective earth (PE) | 
Let me know if you need any support from Muskwell Team. Thanks for your time!

															